3. Summary
A baseline noise survey was undertaken to characterise the existing noise climate within the onshore development area of Berwick Bank Onshore Substation (OnSS). Surveys were undertaken between 7th and 20th May 2021 and between 25th June and 5th July 2021.
The data collected during the baseline noise survey was analysed in order to determine a representative background (LA90) noise level during the daytime and night-time at the identified noise sensitive receptors. Table 14 and Table 15 below shows the representative LA90 determined for each location.
Table 14 – Baseline Noise Data Summary, Daytime
Receptor Identifier | Average, dBLA90,15min | Mode, dBLA90,15min | Standard Deviation | Determined Representative LA90 |
---|---|---|---|---|
SSR1 | 34 | 31 | 4.8 | 31 |
SSR2 | 46 | 48 | 6.3 | 45 |
SSR3 | 33 | 32 | 3.6 | 31 |
SSR4 | 46 | 44 | 2.5 | 44 |
SSR5 | 36 | 35 | 4.2 | 34 |
SSR6 | 35 | 33 | 4.2 | 33 |
Table 15 – Baseline Noise Data Summary, Night-time
Period | Average, dBLA90,15min | Mode, dBLA90,15min | Standard Deviation |
|
---|---|---|---|---|
SSR1 | 32 | 32 | 5.0 | 30 |
SSR2 | 35 | 31 | 5.6 | 30 |
SSR3 | 29 | 31 | 3.4 | 28 |
SSR4 | 45 | 44 | 2.4 | 44 |
SSR5 | 31 | 31 | 4.8 | 28 |
SSR6 | 34 | 35 | 4.0 | 33 |